ZHANG Caijun, QUAN Fengyun, CHEN Jia, et al. Analysis of Cable Sheath Overvoltage Due to Main Transformer No-load Closing[J]. High voltageapparatus, 2019, 55(2): 164-170.
ZHANG Caijun, QUAN Fengyun, CHEN Jia, et al. Analysis of Cable Sheath Overvoltage Due to Main Transformer No-load Closing[J]. High voltageapparatus, 2019, 55(2): 164-170. DOI: 10.13296/j.1001-1609.hva.2019.02.023.
Analysis of Cable Sheath Overvoltage Due to Main Transformer No-load Closing
overvoltage appeared due to electromagnetic oscillation
if there are high voltage cables in the system
internal overvoltage can couple to the cable sheath which results in sheath’s high voltage
and this voltage is related to cable arrangement and sheath grounding method.This article aim at the abnormal discharge phenomena in cable ends of Bailianhe Pumped Storage Station when transformer closes in no-load situation
transformer no-load closing overvoltage is measured
discharge phenomena is observed
and ATP/EMTP software is adopted to calculate cable sheath overvoltage coupled by no-load closing overvoltage.Measurement results show that the no-load closing overvoltage of main transformer is not high
then calculation results show that cable sheath overvoltage in the discharge place is 21.49 kV
with the maximum frequency 600 kHz
which is greater than the arrester operation voltage
this high frequency current flowing into the ground results in ground potential rising at cable bracket
which cause the air gap between the cable sheath insulation and cable bracket breaking down.