MAO Chen, WU Jingfeng, DUAN Wei, et al. Research of Corresponding Relationship Between Transformer Winding Deformation and Variation of Equivalent Electrical Parameters[J]. High voltageapparatus, 2019, 55(2): 183-188.
MAO Chen, WU Jingfeng, DUAN Wei, et al. Research of Corresponding Relationship Between Transformer Winding Deformation and Variation of Equivalent Electrical Parameters[J]. High voltageapparatus, 2019, 55(2): 183-188. DOI: 10.13296/j.1001-1609.hva.2019.02.026.
Research of Corresponding Relationship Between Transformer Winding Deformation and Variation of Equivalent Electrical Parameters
The corresponding relationship between the transformer winding deformation and the variation equivalent electrical parameters has important influence on the accuracy of diagnosis of transformer winding deformation.The corresponding relationship between the winding structure and the equivalent electrical parameters is obtained by establishing the equivalent circuit model of transformer winding.On this basis
one transformer is taken as an example and the plastic deformation state
stress and the axial and radial displacement of the transformer winding under the action of short circuit electromagnetic force are calculated respectively using the electromagnetic-structure coupled finite element method
according to the elastic-plastic mechanics principle.The energy method is used to calculate the winding equivalent circuit electrical parameters of the different type and level of winding deformation
and thus the corresponding relationship between the different type and level of winding deformation and winding equivalent circuit electrical parameters is achieved.The research results can provide reference for diagnosis of deformation state of transformer winding based on the change of equivalent circuit parameters
so as to improve the diagnostic accuracy of transformer winding deformation.