Insulation Condition Evaluation of Contaminated Disc Insulator for Transmission Lines Based on the Characteristic of Discharge UV Imaging Characteristics
|更新时间:2025-04-26
|
Insulation Condition Evaluation of Contaminated Disc Insulator for Transmission Lines Based on the Characteristic of Discharge UV Imaging Characteristics
High VoltageApparatusVol. 55, Issue 2, Pages: 201-207(2019)
WANG Shenghui, NIU Leilei, LI Hao, et al. Insulation Condition Evaluation of Contaminated Disc Insulator for Transmission Lines Based on the Characteristic of Discharge UV Imaging Characteristics[J]. High voltageapparatus, 2019, 55(2): 201-207.
WANG Shenghui, NIU Leilei, LI Hao, et al. Insulation Condition Evaluation of Contaminated Disc Insulator for Transmission Lines Based on the Characteristic of Discharge UV Imaging Characteristics[J]. High voltageapparatus, 2019, 55(2): 201-207. DOI: 10.13296/j.1001-1609.hva.2019.02.029.
Insulation Condition Evaluation of Contaminated Disc Insulator for Transmission Lines Based on the Characteristic of Discharge UV Imaging Characteristics
Insulator is one of the main electrical equipment in power grid.Pollution flashover of insulators seriously threatens the safety and stability of power system.It is of great significance to mater the insulation status of polluted insulators timely.In this paper
the frame is extracted from the ultraviolet video of insulator discharge
the extracted image is segmented by ultraviolet spot
the of spot region area and its time series are calculated
and the relationship between the spot area and leakage current in different discharge stages is analyzed
based on which the insulating state of insulator is given and flashover warning is carried out.An artificial fog chamber with continuously adjustable humidity was constructed.Video of discharging contamination of disc insulators was recorded by UV imager.The ultraviolet characteristics of discharging were extracted.Combining with naked eye observation
leakage current signal and other related parameters
the insulating state of insulators was divided into four stages:"safe"
"warning"
"alarm"and"dangerous".The arithmetic mean
maximum
standard deviation and discharge frequency of the spot area sequence were extracted
and the sample data were analyzed and clustered.The practical application of the project shows that the spot area sequence is effective for the insulation condition assessment of insulators.