ZHAO Zhigang, WEI Peng, LI Xue, et al. Application of Non-oriented Silicon Steel Plate in Magnetic Shielding of Power Transformer[J]. High voltageapparatus, 2019, 55(2): 238-244.
ZHAO Zhigang, WEI Peng, LI Xue, et al. Application of Non-oriented Silicon Steel Plate in Magnetic Shielding of Power Transformer[J]. High voltageapparatus, 2019, 55(2): 238-244. DOI: 10.13296/j.1001-1609.hva.2019.02.035.
Application of Non-oriented Silicon Steel Plate in Magnetic Shielding of Power Transformer
In order to study the applicability of non-oriented silicon steel plate in the power transformer magnetic shield
we study the stray loss and magnetic flux distribution in different excitation conditions
based on the magnetic shielding benchmark model P21 c-M1 and P21-M1 in the international TEAM Problem 21 benchmark family
comparing with magnetic shield made of non-oriented silicon steel plate in the traditional power transformer.The results show that non-oriented magnetic shield made of non-oriented silicon steel has the same shielding effect on the power transformer tank wall which is made of magnetic steel plate
comparing with oriented magnetic shield
and its price is lower.At the same time
based on stray loss in silicon steel lamination
this paper presents a method combining measurement and simulation.By comparing with the traditional stray loss measurement method
the effectiveness of the stray loss calculation method is verified.