Analysis and Optimization on Power-frequency Electric Field of Conductors in 750 kV Substation Based on Sub-model Method
To analyze the corona onset around the conductor in a 750 kV substation in Gansu Province
an entire3 D model of single-pitch conductor is built with the software package Pro/E
and the whole electric field is calculated with finite element method. Then
the typical sub-models of such as jumper and fitting in the substation arebuilt individually
and the electric field is calculated more accurately by refine-meshing. Finally
the reason of on-set corona is analyzed and some suggestions of optimization are offered. Calculation result shows that:(1)the electricfield strength reduces with increasing split number of conductor
which is similar to that of 2 D model;(2)the maxi-mum field strength around jumper is optimized by replacing two-split conductor with four-split conductor
and themaximum value reduces from 2 512.54 V/mm to 2 410.36 V/mm
satisfying the limiting value;(3)compared with the T-mode six-to-two fitting
the improved six-to-two fitting reduces the surrounding electric-field strength by 1 174.79 V/mm