Calculation for AC Resistance of Overhead-line Conductor Based on Magnetic Properties Analysis
AC resistance of overhead-line conductor has a direct effect on transmission capacity and line loss. In this paper the equivalent circuit model of overhead-line conductor used to calculate alternating current resistance presented by Barrett is improved and then called the magnetic properties analysis method. The improvements in-clude the considerations of the change of complex permeability with temperature
the conductivity of steel-core
the temperature difference between the different layers of aluminum conductor
and arc - shaped current element matched with magnetic flux calculated area boundary. The AC/DC ratios of a kind of aluminum conductor rein-forced with aluminized steel core(ACSR/AZ)are calculated by the magnetic properties analysis method
the Mor-gan method and the method of JCS 0374 respectively
the results show the value accounted by the magnetic proper-ties analysis method is smallest
and is considered to be closest to practice in theory.