SUN Xiaodong, LI Ruifang, CAO Xiaobin, et al. Influence of MOA on Lightning Protection of Contact Rail of Metro Viaduct Section[J]. High voltageapparatus, 2019, 55(3): 127-133.
SUN Xiaodong, LI Ruifang, CAO Xiaobin, et al. Influence of MOA on Lightning Protection of Contact Rail of Metro Viaduct Section[J]. High voltageapparatus, 2019, 55(3): 127-133. DOI: 10.13296/j.1001-1609.hva.2019.03.020.
Influence of MOA on Lightning Protection of Contact Rail of Metro Viaduct Section
To reveal the influence of MOA on lightning protection of metro viaduct section contact rail
the elec-tromagnetic transient simulation program is employed to analyze the effects of lightning stroke position and MOA erection method on the lightning withstand level of the contact rail
and the change rules of lightning discharge current and specific energy of MOA under different grounding resistance of bridge pier are obtained. The results show that: ① at the locations from No.1 to No.5 in the lightning protection belt
the grounding resistance of bridge pier imposes weak effect on the lightning withstand level
but at the No.6 location the grounding resistance imposes a great effect and becomes stable; ② erection of MOA can improve the lightning withstand level of the contact rail obviously
and the lightning withstand level rises with the increase in the erection density of MOAs;③ the discharge current and the specific energy of MOA are proportional to the grounding resistance. The YH5WS-17/45 MOA with lower residual voltage is suggested for engineering application.