FAN Weinan, WANG Yong, QIN Yu, et al. Diagnosis and Analysis of Abnormal Thermal Defect in a 220 kV Oil-immersed Inverted CT[J]. High voltageapparatus, 2019, 55(3): 245-252.
FAN Weinan, WANG Yong, QIN Yu, et al. Diagnosis and Analysis of Abnormal Thermal Defect in a 220 kV Oil-immersed Inverted CT[J]. High voltageapparatus, 2019, 55(3): 245-252. DOI: 10.13296/j.1001-1609.hva.2019.03.038.
Diagnosis and Analysis of Abnormal Thermal Defect in a 220 kV Oil-immersed Inverted CT
Infrared detection is one of the important on-live detection techniques for current transformer(CT). By usingthis technique
most cases of the overheating and discharge faults of CT can be detected and diagnosed quickly
therebypreventing certain failures. In this paper
the quality and efficiency of the on-live infrared detection for the CTs inGuangzhou electric power company since 2005 is analyzed firstly. It indicates that the on-live infrared detection can de-tect the faults of the high voltage current transformer effectively. Then a family defect of a 220 kV inversion current trans-former found by an infrared live detection is analyzed in detail. Combined with dielectric loss test
insulation oil test andpartial discharge(PD)test
a comprehensive diagnosis of the abnormal current transformer is carried out
and the exis-tence of the internal defects in the abnormal CT is clearly defined. Finally
through the maintenance the defects in the ab-normal CT are found
such as lack of oil inside the expander and folds and foamy foreign body inside the expander.