GAO Chaofei, SONG Shu, TONG Zhongyu, et al. Partial Discharge Location in Oil Based on EFPI Optical Fiber Ultrasonic Sensor[J]. High voltageapparatus, 2019, 55(4): 90-95+101.
GAO Chaofei, SONG Shu, TONG Zhongyu, et al. Partial Discharge Location in Oil Based on EFPI Optical Fiber Ultrasonic Sensor[J]. High voltageapparatus, 2019, 55(4): 90-95+101. DOI: 10.13296/j.1001-1609.hva.2019.04.013.
Partial Discharge Location in Oil Based on EFPI Optical Fiber Ultrasonic Sensor
Extrinsic fabry-perot interferometric(EFPI) optical fiber ultrasonic sensor has high sensitivity and is not affected by electromagnetic interference. This paper applies it to partial discharge(PD) localization in oil. First a 2×2 EFPI ultrasonic sensor array is designed
which can be placed in the oil to detect PD ultrasonic signal. Then according to the steered response power(SRP) sound source localization theory to locate PD. Finally SRP and MUSIC(multiple signal classification) algorithms are used to process the experimental signals and compared. The results show that the EFPI sensor array can detect the partial discharge signal with high SNR in the oil. The SRP algorithm has less error than the MUSIC algorithm and can locate PD according to a single measurement
but the positioning accuracy should be further improved. The method proposed in this paper has reference significance for the practical application of EFPI optical fiber ultrasonic sensor in partial discharge positioning of electrical equipment.
Research on Application of Microphone-optimized Spiral Arrays-based Acoustic Imaging Devices in Partial Discharge Localization
Study on Fiber Interferometric Partial Discharge Ultrasonic Sensing Method Based on Acoustic-optic Modulation and RF Phase Detection
High-frequency Sensing Technology of Partial Discharge of Switchgear Cabinet for Wind Solar & Energy Storage Stations in Gobi Deserts
Research on Influence of Piezoelectric Material Properties and Element Size on Sensitivity of Piezoelectric Sensor for Partial Discharge Monitoring of Transformer
Influence of Environmental Factors on Insulation Performance of Separable Connector for 12 kV Gas Filling Switchgear Cabinet
Related Author
YUE Song
GAO Fei
HAN Shuai
DONG Haoyuan
LI Jun
LI Xin
LIU Chao
QIAO Hui
Related Institution
Electric Power Research Institute of State Grid Tibet Company
China Electric Power Research Institute Co., Ltd.
Iflytek Co., Ltd.
Electric Power Research Institute, State Grid Hebei Electric Power Co., Ltd.
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University