CHEN Qing, XUE Yuan, WANG Ke, et al. Research on Overvoltage and Insulation Coordination of Flexible DC System for Offshore Wind Farm Integration[J]. High voltageapparatus, 2019, 55(4): 178-184.
CHEN Qing, XUE Yuan, WANG Ke, et al. Research on Overvoltage and Insulation Coordination of Flexible DC System for Offshore Wind Farm Integration[J]. High voltageapparatus, 2019, 55(4): 178-184. DOI: 10.13296/j.1001-1609.hva.2019.04.025.
Research on Overvoltage and Insulation Coordination of Flexible DC System for Offshore Wind Farm Integration
flexible DC system is gradually becoming the mainstream scheme for large-scale offshore wind farm integration. Considering the lack of related research at home and abroad
this paper analyzes the overvoltage protection and insulation coordination of flexible DC system on this occasion. First
the basic layout of the flexible DC system is introduced
including the topology
the main electrical equipment in converter station and the grounding schemes. Second
basic principles for studying the overvoltage protection and insulation coordination are discussed
which mainly involves the selection of the typical fault
the voltage observation point
and the configuration scheme of arresters. Last
based on a planning ±320 kV/1 100 MW flexible DC system for wind farm integration
the simulation is carried out on PSCAD/EMTDC
and the overvoltage characteristics are studied. The paper also determined the insulation levels of the main electrical equipment. The research conclusions fill the gap in this field
which could serve as an important reference for similar practical projects in the future.