Analysis of Influence of Lightning Strike Transmission Line on Parallel 10 kV Distribution Line
10 kV distribution lines may parallel with transmission lines due to the limit of line corridor
so it is necessary to study the interference on 10 kV distribution line when lightning strikes on the parallel transmission line.Shielding effect of transmission lines and interference of transmission line under lightning on distribution line are analyzed. Coupled electrical circuits of distribution lines and transmission lines are also established in EMTP to calculate induced overvoltage on the distribution line. Effects of height of the shielding line
distance and height difference of the transmission line from the distribution line and ground resistance of the transmission tower on induced overvoltage are discussed. The results show that: induced overvoltage on the distribution line decreases as the increment of height of the shielding line and distance of the transmission line from the distribution line of the height difference
but change trends of induced overvoltage are opposite. Induced overvoltage increases with the rise of ground resistance of the transmission tower. Bad grounding of the transmission tower will result in insulation problem
so it is necessary to reduce the ground resistance as low as possible.