SHI Zhiqiang, DENG Wei, LUO Richeng, et al. Relation Between Moisture and Electrical Parameters of Zinc Oxide Arrester[J]. High voltageapparatus, 2019, 55(4): 233-238+244.
SHI Zhiqiang, DENG Wei, LUO Richeng, et al. Relation Between Moisture and Electrical Parameters of Zinc Oxide Arrester[J]. High voltageapparatus, 2019, 55(4): 233-238+244. DOI: 10.13296/j.1001-1609.hva.2019.04.033.
Relation Between Moisture and Electrical Parameters of Zinc Oxide Arrester
For the purpose of monitoring the status of MOA which is in services effectively and discover the potential causes of accidents of MOA timely
which is able to prevent the accidents from being expanded. The variation in the electrical parameters of 500 kV zinc oxide arrester that is tested under different moisture positions is studied in the lab. The relationship between the full current
the resistive current component
the third harmonic of the resistive current
the fifth harmonic of the resistive current
the active power loss and the phase angle on the sensitivity of the surge arrester(zinc oxide) is analyzed. The experimental results show that the variation of the electrical parameters of MOA is different under different moisture positions; the total current
the phase angle are not sensitive to the moisture sensitivity of MOA
which can only be used as the basis for the judgment of MOA moisture; the combination of resistive current component and third harmonic current can be used as a basis for judging the location of MOA; the fifth harmonic of resistive current and the active power loss have a high sensitivity to MOA
which can be used as an important parameter to monitor the running state of MOA. In this paper
the electrical parameters of 500 kV MOA under different moisture positions are tested and analyzed in the laboratory. Because of the difference between the ambient environment and the laboratory environment of the actual operation of zinc oxide arrester
the conclusions obtained in this paper are for reference only.