Fault Diagnosis of Large-capacity Transformer After Short-line Short-circuit Current Surge
This article describes the process of fault diagnosis of a larg-capacity three-winding transformer that has been impacted by a short-line short-circuit current. It is pointed out that the transformer windings are affected by the electrical stress generated by the inrush current
which causes the transformer to shift and deform
resulting in changes in the capacitance between windings and between windings and the ground. This is compared with the historical data of the transformer capacitance or the capacitance data of the same type of transformer. It can quickly and effectively find the transformer winding displacement deformation failure.