Experimental Research on Flashover Characteristics of Insulator with N2
becomes an alternative gas because of its abundant resources
low price
environmental friendliness and good insulation performance. In this paper
flashover characteristics of insulator with N
2
are tested and 50% flashover voltage under lightning impulse is measured. The results show that flashover voltage increases approximately linearly with the increase of the pressure.With the increase of the surface roughness of the insulator
the flashover voltage decreases first and then increases. With the increase of umbrellas’ number
the flashover voltage under positive lightning impulse doesn’t chan
ge basically
while the negative flashover voltage first decreases a lot and then rises. The results and conclusions in this paper can provide a reference for the application of N