SUN Xu, CAO Shidong, LEI Xiao, et al. Control Strategy Research on ±500 kV Flexible HVDC Grid[J]. High voltageapparatus, 2019, 55(5): 154-160. DOI: 10.13296/j.1001-1609.hva.2019.05.024.
Control Strategy Research on ±500 kV Flexible HVDC Grid
±500 kV flexible HVDC grid control strategy is researched and analyzed. The converter is need to avoid connecting to the weak AC grid under SCR less than 1.3 according to converter level strategy. The system strategy is very important and it must focus on both system stability and converter overload. The rated voltage converter can charge for the other converters by DC break and the disturbance should be acceptable. The rapid close loop switches can be installed to loop the DC grid line flow.