ZHU Xinyao, ZHAO Jingbo, LIU Jiankun, et al. SSO Characteristics of Doubly Fed Wind Farm Integrated by Hybrid Series Compensator[J]. High voltageapparatus, 2019, 55(5): 194-200.
ZHU Xinyao, ZHAO Jingbo, LIU Jiankun, et al. SSO Characteristics of Doubly Fed Wind Farm Integrated by Hybrid Series Compensator[J]. High voltageapparatus, 2019, 55(5): 194-200. DOI: 10.13296/j.1001-1609.hva.2019.05.030.
SSO Characteristics of Doubly Fed Wind Farm Integrated by Hybrid Series Compensator
wind farms with DFIG(doubly fed induction generator) integrated by series compensated AC transmission lines are confronting with the problem of SSO(subsynchronous oscillation). In this paper
the configuration and control strategy of hybrid series compensator composed by SSSC(static synchronous series compensator) and fixed capacitor are proposed
and testing method for subsynchronous frequency equivalent impedance of series FACTS is presented as well. Consequently
subsynchronous frequency impedance characteristics of SSSC are analyzed
and SSO characteristics of DFIG integrated by hybrid series compensator are studied. The results reveal that the subsynchronous frequency equivalent impedance of SSSC is positive
and the SSO damping is larger with higher proportion of SSSC in hybrid series compensator;in addition
the SSO damping is larger with larger compensation impedance or voltage of SSSC. The research is helpful for the planning and operating of the power system with large scale wind farm integrated.