QI Fangfang, WANG Haiyun, CHANG Peng. Analysis on Transient Characteristics of Hybrid DC Transmission Connected-grid System with Wind Power[J]. High voltageapparatus, 2019, 55(5): 201-206.
QI Fangfang, WANG Haiyun, CHANG Peng. Analysis on Transient Characteristics of Hybrid DC Transmission Connected-grid System with Wind Power[J]. High voltageapparatus, 2019, 55(5): 201-206. DOI: 10.13296/j.1001-1609.hva.2019.05.031.
Analysis on Transient Characteristics of Hybrid DC Transmission Connected-grid System with Wind Power
In order to improve the transient stability of the HVDC system
in this paper uses the DFIG based on sending
to establish the LCC-diode-MMC hybrid DC transmission network system
and study the grid-connected transient operation characteristics of the system
the rectifier side using the line commutated converter(line commutated converter
LCC)
inverter side using modular multilevel converter(modular multilevel converter
MMC). In order to solve the problems of the MMC can’t remove the DC fault
install the high power diode at the DC outlet of the inverter side to block the fault current path. In the MATLAB/Simulink platform
LCC-diode-MMC wind power grid simulation model is established. The superiority of LCC and MMC is analyzed by setting the DC and grounding fault. The results show that the system does not have the problem of inverter phase commutation failure and the high-power diode in the system can block the fault current path when the DC fault occurs
during the fault
the DC voltage of the inverter side does not increase and the active power fluctuates very small
thus enhancing the system’s transient stability characteristics.