Countermeasures on Low Temperature for Switchgear in 1 100 kV UHVAC Substation
more and more UHV submission will build at low temperature area. As the insulating medium of UHVAC switchgear
SF
6
is likely to liquefy at low temperature
which may reduce the stability of the switchgear and increase the operation risk of the state grid. It is necessary to take measures to improve the cold-resistant ability of the switchgear. Based on the importance of different switchgear
it is appropriate to carry out indoor installation for 1 100 kV GIS. To some outdoor 1 100 kV busing and bus
reduce the SF
6
pressure can make the liquefaction temperature lower to accommodate the cold environment. To 126 kV GIS and 550 kV
GIS
it is effective to add heating devices around the switchgear
and heat it at certain procedure
which can keep the SF
6
stable. All the measures have been tested by low temperature test. And the result can provide guidance for the latter construction and operation of UHV submission.