Analysis and Status Assessment of Circuit Breaker’s Operation Characteristics Based on Power Dispatching Automation System
Considering the fact that the existing power dispatching automation system pays less attention to operation parameters of circuit breaker
this paper delves into the important operation parameters of a circuit breaker in the power dispatching automation system. The correction parameter of circuit breaker operation time △t and the protector exit delay tdelay are introduced
and their stabilities are evaluated. Subsequently
a model of circuit breaker’s operation time characteristic is established based on the data of power dispatching automation system. A large number of tests verify that the opening and closing time of a circuit breaker based on this model obeys normal distribution.
At last
two status assessment strategies are offered for a 126 kV SF
6
circuit breaker and a medium-voltage vacuum circuit breaker.