AC Discharge Performance and Voltage Correction of Rod-plane Gap Under Low Air Pressure
For the purpose of obtaining rod-plane air gap discharge performance under high altitude and low pressure conditions
laboratory investigations of the relationship between 50% AC discharge voltage U
50
air pressure P and air gap distance d are carried out in the low pressure test platform for 100~600 mm rod-plane gaps. The effects of P and d on U
50
are analyzed in the range of 2 to 60 kPa. The relationship between U
50
P and d are obtained
furthermore
put forward voltage correction formulas of AC discharge within 2~60 kPa. The results show that
U
50
-P curves of different gaps within 2~60 kPa all have obvious saturation t
rends. As gap length decreases
the saturation region moves toward low pressure direction
and the U
50
correction formula based on the experimental data has a high accuracy. The results can provide reference for the study of the discharge characteristics of rod
plane air gap at high altitude and low pressure conditions