DENG Wangbo, WANG Haiyun, CHANG Xiqiang, et al. Analysis of Influencing Factors of Subsynchronous Oscillation in Large-scale Direct-driven Wind Farm[J]. High voltageapparatus, 2019, 55(6): 218-224.
DENG Wangbo, WANG Haiyun, CHANG Xiqiang, et al. Analysis of Influencing Factors of Subsynchronous Oscillation in Large-scale Direct-driven Wind Farm[J]. High voltageapparatus, 2019, 55(6): 218-224. DOI: 10.13296/j.1001-1609.hva.2019.06.032.
Analysis of Influencing Factors of Subsynchronous Oscillation in Large-scale Direct-driven Wind Farm
for large wind farms in Hami area in the series compensated case of subsynchronous oscillation phenomenon
based on PSCAD/EMTDC software
the model of no series compensated transmission system of multi machine direct-drive wind power farm is built
combined with eigenvalue analysis method
the effects of wind speed
parameters of grid-side controller
short circuit ratio of wind power collecting point and output of thermal power unit on the sub-synchronous oscillation characteristics are studied and verified by simulation. The results show that there is no series compensation case
the wind farm may occur in the subsynchronous oscillation in the wind while the wind speed is small
high oscillation frequency
wind speed
low oscillation frequency. The net side controller proportional gain more. Vibration swing frequency is small
the greater the integral gain
oscillation frequency is greater. Short circuit ratio decrease the possibility of system subsynchronous oscillation increases. Low power operation
power units within the range of 50%~80% and the possibility of system subsynchronous oscillation.