Analysis of a Circuit Breaker Inadequate Closing Failure Due to Pin Defect
A circuit breaker poor closing failureis analyzed. Through field inspection
size measurement
fault simulation and metal detection
it is found that the absence or poor installation of the locking piece at the end of the joint pin of hoisting rod and insulation rod causespin displacement and friction with the inner wall of the lower support
which increases the closing resistance and hence results in the inadequate closing failure of the circuit breaker. Accordingly