Research on CF4 Gas Detection Method in GIS Gas Chamber Based on NDIR Technology
In order to realize the on-line real-time detection of CF
4
gas in GIS gas chamber and perfect the defect di-agnosis of high-voltage electrical equipment based on gas chemical composition analysis
the optical CF
4
gas sensoris designed by applying non-dispersive infrared(NDIR)technology. The system adopts a single-beam dual-wave-length structure to determine the type of return light path gas chamber and improve the sensitivity of the system. Interms of hardware
the high performance single chip microcomputer with multi-channel 1
2-bit ADC are adopted tofurther improve the detection accuracy. The test results of multi-group distribution gas system show that the maxi-mum indication error of sensor test of CF
4
gas with different volume fraction before and after temperature compensa-tion by RBF-PSO algorithm is 7.93% and 1.20%
respectively. The ratio of SB/SA between reference signal ampli-tude and measurement channel signal amplitude in the calibration test of CF
4
gas range with different volume fractionis fitted exponentially
and the nonlinear correlation R2 is 0.999 3. The RSD of the sensor is 0.87%
0.44% and0.32%
respectively. In conclusion
the advantages of CF
4
sensor in measuring range
anti-interference ability