FAN Min, WANG Jia, HUANG Haibo, et al. Application of Online Detection in Partial Discharge Test of True Switchgear[J]. High VoltageApparatus, 2019, 55(7): 235-241.
FAN Min, WANG Jia, HUANG Haibo, et al. Application of Online Detection in Partial Discharge Test of True Switchgear[J]. High VoltageApparatus, 2019, 55(7): 235-241. DOI: 10.13296/j.1001-1609.hva.2019.07.034.
Application of Online Detection in Partial Discharge Test of True Switchgear
The most data of online detection are indirect state and strong experience
so they cause the erroneousjudgement of defect easily. Therefore
this paper set up defect simulation test device based on real switch cabinetand simulated pin-to-plate discharge
suspension discharge
surface discharge. Through the comparison of acousticemission
transient earth voltages
ultra high frequency and pulse current
the law of these discharge is found
thetypical map of discharge and the relationship between online detection signal and partial discharge are obtained. It isalso gained that the sensibility of acoustic emission and ultra high frequency is similar
and more than transient earthvoltages. These finds lay the foundation for quantitative analysis of online detection.