Experimental Research and Comparative Analysis on Live Test Methods of Partial Discharge of Internal Defects in 1 100 kV GIS
Live test of partial discharge is one of the most important method to judge internal insulation condition of GIS equipment in UHV substation.In order to analyze the effect of different live test methods
internal defect models were established on the real type testing platform of 1 100 kV GIS.Then simulations and experimental research were carried out on the defect models.According to the test results
the effectiveness of the partial discharge live tests
including ultra-high frequency method
acoustic emission method and high frequency current method
was comparatively evaluated using radar graph.This study may facilitate the research of internal defect features of 1 100 kV GIS equipment
and provide data support to the live detection of GIS equipment in ultra-high voltage substation and to the integrative application of multiple detection methods.