Calculation and Experimental Verification of Cable Support’s Temperature Rise Based on Electromagnetic-fluid-thermal Fields
The application of large-length and large-section power cable in cable tunnel leads to the serious line loss caused by eddy current in cable support and the thermal deformation of cable support.Taking 110 kV single-phase cable and its cable support as research objects and adopting the finite element numerical calculation method to calculate its electromagnetic-fluid-thermal coupling field.The eddy current loss calculated by the electromagnetic field is taken as the heat source load in fluid-thermal field
and the heat dissipation mode of the natural convection of the air is considered
thereby calculating the temperature distribution of the cable support.Finally
temperature rise experiment of cable support is conducted
and the simulation data are compared with the experimental one to verify the accuracy and effectiveness of the temperature rise calculation of cable support.