Dynamic Early-warning Method Based on Dissolved Gas in Oil of 220 kV Transformer
Dissolved gas analysis in oil is one of the most common methods for monitoring the operating state of power transformers.The existing standard set the early-warning threshold for volume fraction of dissolved gas in oil as a fixed and too large value.In response to this problem
a dynamic early-warning method based on data statistics and distribution model is proposed in this paper.Firstly
nearly 100
000 volume fraction data of dissolved gas in oil for220 kV transformer in a certain power grid is statistically and classified
and the volume fraction distribution model of dissolved gas in oil is established.Then
based on the actual volume fraction early-warning data of dissolved gas in oil
the dynamic early-warning value is calculated by the inverse accumulation operation of distribution model.Thus
a dynamic early-warning method for the volume fraction of dissolved gas in oil has been realized.Finally
the dynamic early-warning method is compared with the existing standard and the calculation results of the 10% partition principle and the dynamic characteristics of early-warning threshold is discussed.The results show that this method can reduce missed alarms compared with the existing standard
also can reduce false alarms compared with the 10%partition principle.In other words
a good balance between missed alarm and false alarm has been achieved
which has a certain value of engineering application.