XIE Fei, QU Lu, JIN Huan. Application of Nonlinear Transformer Theory in HVDC Fault Current Limiter[J]. High voltageapparatus, 2019, 55(9): 57-63. DOI: 10.13296/j.1001-1609.hva.2019.09.008.
Application of Nonlinear Transformer Theory in HVDC Fault Current Limiter
Fault current limiter(FCL)is a sort of quasi-transformer that inhibits short-circuit current and protect neutral beam injector in the system of the experimental advanced superconducting TOKAMAK(EAST).Starting from the eddy-current loss properties of transformer core disk
this paper adopted the piecewise linear interpolation method to optimize the HVDC FCL non-linear hysteresis loop and derive a nonlinear exciting resistance-inductance parallel model.A comparative analysis of simulation and experimental results indicates the optimized hysteresis loop model’s simulation waveform fits well with the experimental results
and short-circuit current suppression effect is good.