Feasilibility Study on Partial Discharge IED Performance Test of Intelligent GIS with Sub-nanosecond Pulse
Gas-insulated metal-enclosed switches(GIS)have been widely used in power system due to their small floor area and high reliability.However
in the long-term operation of GIS
various internal insulation defects are inevitably generated and partial discharge phenomenon may occur concomitantly
which may even cause system failure.Therefore
in order to ensure the reliable operation of the system
it is of great significance to perform partial discharge on-line monitoring of GIS.Partial discharge detection has various detection methods such as electrical
acoustical
chemical and optical.Among them
electrical measurement methods mainly include pulse current method and ultra-high frequency(UHF)method.UHF method measures the electric field strength of electromagnetic waves emitted by partial discharge
while the pulse current method measures the apparent charge caused by partial discharge.The UHF method can extract the UHF components in the signal compared with the pulse current method
which has high sensitivity and can be monitored on-line.The intelligent GIS PD IED(intelligent electronic device)adopts the UHF+IED partial discharge monitoring method.In this paper
the feasilibility is studied that the sub-nanosecond pulse with a rising edge time of 253.75 ps
the FWHM is about 1.15 ns and a maximum peak voltage of 532 V(0 d B)is used to test the IED performance of the intelligent GIS.The results show that the output signal of UHF sensor is steady
IED displays positively correlation with the peak value of the sub-nanosecond pulse rather than a linear relationship
when the sub-nanosecond pulse is 30~50 dB
the results of IED are highly dispersed
so the sub-nanosecond pulse can be used to test the partial discharge IED performance test of intelligent GIS.