GENG Leizhao, LIU Ronghai, TANG Faqing, et al. Application of X-ray Image Size Calibration Technology in GIS Fault Analysis[J]. High voltageapparatus, 2019, 55(9): 119-125.
A fault of GIS equipment circuit breaker in a 500 kV substation was analyzed.First
the X-ray digital imaging technology was used to detect the faulty circuit breaker
and the X-ray image size calibration technology was employed to accurately obtain the stroke size of the circuit breaker’s operating mechanism.Then
accurate analysis on the dimensional relations of the circuit breaker helped to find the loosened fixed bolt on the mounting plate of the circuit breaker
which caused a slight upward slope or horizontal displacement of the mounting plate
leading to insufficient switching of the circuit breaker.This work shows that the X-ray image size calibration technology can be applied to GIS fault analysis
especially can provide accurate size data for circuit breaker and other operating mechanisms.