Aging Phenomena and Condition Assessment Method of RTV Anti-pollution Flashover Coating
Room temperature vulcanized(RTV)silicone rubber has been widely used as anti-pollution flashover coating in power system.During long-term operation
aging phenomena such as peeling off
color fading and chalking could occur
hence leading to the loss of anti-pollution performance.In this paper
RTV coating used in different environments are sampled and test results show that reduction of organic functional group and increase ofobserved.It is concluded that thermal stability and organic component decreases when RTV coating ages and X-ray diffraction analysis could be applied for its condition assessment.
Contrastive Study on Microscopic Characteristics of DC Composite Bushing’s LSR Shed Chalking Layer and Inner Layer
Method on Distinguishing Aging and Deterioration Condition of Insulation and Semi-conductive Materials via Channel Characteristics of Medium Voltage Cable
Study on Mechanical Property Variation of EPDM Sealing Materials for GIS Equipment Before and After Aging
ANALYSIS ON THE EVALUATION METHOD OF AGING FOR COMPOSITE INSULATORS
Study on Aging Characteristics of Insulation in Inverter-fed Traction Motor Based on Dielectric Loss
Related Author
YAN Nianping
XU Chi
CHEN Can
JIA Zhidong
CHEN Jie
LIU Jian
HU Libin
WANG Yuli
Related Institution
State Grid Jiangxi Electric Power Research Institute
Department of Electrical Engineering, Tsinghua University
Graduate School of Tsinghua University
Wuhan Branch of China Electric Power Research Institute Co., Ltd.
State Grid Jiangsu Electric Power Co., Ltd. Electric Power Research Institute