ZHOU Chenmeng, LUO Richeng, WU Dong, et al. Analysis of Equipotential Operation Mode of Live Working on Small Angle Tower of ±800 kV Transmission Line[J]. High voltageapparatus, 2019, 55(9): 179-186.
ZHOU Chenmeng, LUO Richeng, WU Dong, et al. Analysis of Equipotential Operation Mode of Live Working on Small Angle Tower of ±800 kV Transmission Line[J]. High voltageapparatus, 2019, 55(9): 179-186. DOI: 10.13296/j.1001-1609.hva.2019.09.024.
Analysis of Equipotential Operation Mode of Live Working on Small Angle Tower of ±800 kV Transmission Line
推荐作业人员采用吊篮法的方式进出等电位;作业人员进出等电位的过程中应穿戴屏蔽效率为60 dB、配有金属丝面罩的直流特高压专用屏蔽服。以上结论能为±800 k V直流输电线路小转角塔带电作业的顺利开展及安全防护措施的制定提供理论依据。
Abstract
In order to ensure the safe of live working of±800 kV DC transmission line
combined with the engineering practice
an equal scale model of small angle tower for HVDC transmission lines is constructed.The values of field strength of the body surface in two different operation modes are calculated by using ANSOFT software.The recommended methods and paths in the process of equipotential handling are analyzed and obtained
and then the safety measures should be taken by the electrified operators.The results show that when using a hanging basket for equipotential operation
the average intensity of workers body is smaller than the soft ladder way
according to the degree of fatigue and operability of operation methods
it is recommended that operators use the hanging basket method to enter and exit equipotential;When performing equipotential operation
the operator shall wear a direct current ultra-high voltage shielding shield with a shielding efficiency of 60 dB and a metal wire mask.The above conclusions provide a theoretical basis for the live working on the small angle tower of±800 kV DC transmission line.
Research on Human Digital Twins for Live Working on Transmission Lines Based on Attitude Estimation
Study on the Amplitude and Energy Characteristics of the in and out of Equipotential Pulse Current for 1000 kV Transmission Line Tension Tower Based on HHT
Live Working Insulation Blanket Surface Defect Recognition Based on Improved YOLOv8
Insulation Protection Design of Live working Robot for 10 kV Distribution Power Systems
Feasibility Research of Live Working on 500 kV Compact Line
Related Author
ZHANG Chengwu
XU Jinshuai
WANG Wei
MA Aiqing
WU Tian
SONG Xuan
PENG Yong
QIU Zhonghua
Related Institution
School of Electrical Engineering, Shanghai University of Electric Power
State Grid Sichuan Extra High Voltage Company
China Electric Power Research Institute
Hubei Provincial Engineering Technology Research Center for Power Transmission Line, China Three Gorges University
College of Electrical Engineering & New Energy, China Three Gorges University