Cause Analysis on Subsynchronous Oscillation in Large-scale Doubly-fed Wind Farm
To explore the reason why subsynchronous oscillation occursinlarge-scale doubly-fed wind farm without series compensation
the software MATLAB/Simulink is employed to build a grid model of doublely-fed wind turbinewith series compensation.The relations of the subsynchronous oscillation with the wind turbine output
the parameters of RSC controller and outer-loop reactive powercontroller
and the length of transmission line are investigatedbased on the time-domain simulation method.The results show that with the increase in the wind speed and turbine number in grid
the wind turbine output becomes larger
hence the subsynchronous oscillation is prone to occur.Only changing theof the RSC inner-loop current controller does not result in system oscillation
but if theis too large
the subsynchronous oscillation may happen more likely.If theproportional coefficient Kpof the outer-loop reactive power controller is too large or the parameters of the controller are too sensitive
the reactive power would be overshot and subsynchronous oscillation would happen more easily.The size of the transmission line only affects the range of voltage fluctuation