Electric Field Simulation of the 363 kV Multi-break Fast Vacuum Circuit Breaker
Aiming at the application of vacuum circuit breaker(VCB)in the 363 kV power grid
a new multi-breakVCB with series and parallel configuration is proposed. According to the actual design structure of single circuit breaker
a 3D electric field analysis model including multiple dielectrics is established. The finite element method is used to calculate the electric field distribution. The insulation strength of the grading ring
insulator
interrupter and grading capacitor is analyzed. Results of calculation under rated voltage show that the maximum electric fields of the grading ring and insulators are 1.23 kV/mm and 0.48 kV/mm
respectively
and the electric fields of the interrupter and grading capacitor are under 0.4 kV/mm. The electric field of the whole 363 kV VCB is in the control range
and the calculation results can be taken as a reference for the optimization and production of the prototype.