Simulation Study on Transient Over-voltage in Power Collection Network of Offshore Wind Farm Considering Prestrike Characteristics of Vacuum Circuit Breaker
|更新时间:2025-04-26
|
Simulation Study on Transient Over-voltage in Power Collection Network of Offshore Wind Farm Considering Prestrike Characteristics of Vacuum Circuit Breaker
High VoltageApparatusVol. 55, Issue 10, Pages: 38-43(2019)
WU Junchen, WANG Lingjiao, REN Zhihua, et al. Simulation Study on Transient Over-voltage in Power Collection Network of Offshore Wind Farm Considering Prestrike Characteristics of Vacuum Circuit Breaker[J]. High voltageapparatus, 2019, 55(10): 38-43.
WU Junchen, WANG Lingjiao, REN Zhihua, et al. Simulation Study on Transient Over-voltage in Power Collection Network of Offshore Wind Farm Considering Prestrike Characteristics of Vacuum Circuit Breaker[J]. High voltageapparatus, 2019, 55(10): 38-43. DOI: 10.13296/j.1001-1609.hva.2019.10.007.
Simulation Study on Transient Over-voltage in Power Collection Network of Offshore Wind Farm Considering Prestrike Characteristics of Vacuum Circuit Breaker
In closing operation of vacuum circuit breaker for no-load transformer in medium-voltage cable power collection grid of offshore wind farm
the prestrike of the vacuum circuit breaker will produce transient over-voltage on the high-voltage side of the generator transformer
and this over-voltage
interacting with the cable
will produce high-frequency oscillation over-voltage to cause damage to the transformer insulation. In order to reveal the producing mechanism of high-frequency transient over-voltage in prestrike of the vacuum circuit breaker
this study employs the transient analysis software PSCAD/EMTDC to build a self-defined model which can reflect the prestrike phenomenon of vacuum circuit breaker. This model is applied to a simplified simulation model of the medium-voltage cable power collection grid of offshore wind farm to analyze the influences of initial phase angle of closing
cable length and generator transformer position on the transient over-voltage. Simulation results show that the over-voltage steepness is the largest when the generator transformer is located in the engine room and the initial phase angle is 15°
and the transient over-voltage steepness is obviously suppressed after the over-voltage protection device including choke and parallel small capacitor is installed on the generator transformer.