Research of Timing Testing Method on Circuit Breakers with Both Sides Grounded
Timing test for high voltage circuit breaker is used to evaluate the condition of mechanical components of circuit breakers and phase synchronizations. Safety regulation requires the circuit breaker under maintenance must be grounded on both sides to avoid the damage caused by high induced voltage. However
one grounded side has to be removed before carrying out conventional timing test due to low resistance of ground circuit. In this paper
the risk of testing one side grounded circuit breaker is analyzed. Then some commonly used new technology
the dynamic resistance measurement(DRM)
as well as two high frequency technologies are introduced. After theoretical analysis
experiment and field testing
the dynamic capacitance measurement(DCM)technology which is based on the variable frequency resonance is the most reliable dual ground testing method. It is able to give timing results highly consistent with that from the conventional method. Meanwhile
the DCM method can be used to test the GIS breakers safely and efficiently.