On-line Double-ended Power Cable PD Location Method Based on Phase Difference Algorithm of Optimized Pulse Time Window
Conventional phase difference method pinpoints the PD location by analyzing the phase difference of the primary arriving signals at both terminals in power cable under frequency domain
however it takes the maximum propagation time of pulses as the time window length
which inevitably results in redundant interference in the signal processing and therefore reduces the location accuracy. Based on double-sided phase difference algorithm of optimized time window length
an improved on-line PD location method is proposed. The start and end time points of double-sided pulses are identified when pulse passed the configured amplitude threshold. By means of setting up time margin of rising and falling edge
the removed pulse information before and after are recovered and the optimized time window is then obtained. Afterwards
the matched double-sided pulses captured by the time window calculated before is processed by cross-correlation analysis and Fourier transform
and the defect location from single sample is then determined by phase unwrapping algorithm. Cluster analysis using D-Peak method is adopted to realize the automatic identification of PD clusters from large quantities of PD location results and the horizontal position of cluster center refers to the final PD location. The performance of the proposed technique is evaluated by simulation using ATP-EMTP under noisy environment and experimental test using XLPE cable of 300 m. The results show the improvement of PD location accuracy compared to traditional double-sided phase difference and time-of-arrival approach.
Classification of Partial Discharge Pulses Based on Waveform Characteristics and Statistical Parameters
Research on Application of Microphone-optimized Spiral Arrays-based Acoustic Imaging Devices in Partial Discharge Localization
Study on Fiber Interferometric Partial Discharge Ultrasonic Sensing Method Based on Acoustic-optic Modulation and RF Phase Detection
High-frequency Sensing Technology of Partial Discharge of Switchgear Cabinet for Wind Solar & Energy Storage Stations in Gobi Deserts
Research on Influence of Piezoelectric Material Properties and Element Size on Sensitivity of Piezoelectric Sensor for Partial Discharge Monitoring of Transformer
Related Author
XIA Yunfeng
GAO Shengyou
CHEN Xiyang
GUI Junfeng
HE Wen
YANG Qiaoyuan
YUE Song
GAO Fei
Related Institution
Dongguan Power Supply Bureau of Guangdong Power Grid Corporation
Dept.of Elec.Eng.,Tsinghua University,State Key Lab of Control and Simulation of Power Systems and Generation Equipments
School of Elec. Eng.,Beijing Jiaotong University
Electric Power Research Institute of State Grid Tibet Company