WU Jinyuan, XIA Guoqiang, LI Tong, et al. Assessment of Aging State of Transformer Oil-paper Insulation Based on Time Domain Dielectric Method and Dynamic Bayesian Network[J]. High voltageapparatus, 2019, 55(10): 196-203.
WU Jinyuan, XIA Guoqiang, LI Tong, et al. Assessment of Aging State of Transformer Oil-paper Insulation Based on Time Domain Dielectric Method and Dynamic Bayesian Network[J]. High voltageapparatus, 2019, 55(10): 196-203. DOI: 10.13296/j.1001-1609.hva.2019.10.032.
Assessment of Aging State of Transformer Oil-paper Insulation Based on Time Domain Dielectric Method and Dynamic Bayesian Network
In order to make an accurate assessment of the oil-paper insulation aging state of transformers
six characteristic quantities are extracted based on polarization/depolarization current method.Dynamic Bayesian network is introduced into the assessment of oil-paper insulation aging state
and an aging step prediction model that verified by the experiment is established.The results indicate that:the quantity of insulation paper electricity Q
paper
the stable average conduction current ■
and the average polarization characteristic time ■ are sensitive to oil-paper insulation aging state
and fit well
with the degree of polymerization
so that
these can be used as characteristics to represent the aging of insulation paper.The assessment of oil-paper insulation is in accordance with the application conditions of dynamic Bayesian network
by dividing the characteristics state and aging stage
it can reflect the timing relationship between variables.The accuracy of the assessment model of oil-paper insulation aging state is 91.3%
relative average error is 0.108.So the accuracy and stability of applying dynamic Bayesian network to the assessment of oil-paper insulation aging state.