DENG Jianqing, BAI Xiaoping, QIU Jiqing, et al. Analysis and Prevention Measures of Discharge Research of Insulated Pull Rod in GIS Disconnector[J]. High voltageapparatus, 2019, 55(10): 247-252.
DENG Jianqing, BAI Xiaoping, QIU Jiqing, et al. Analysis and Prevention Measures of Discharge Research of Insulated Pull Rod in GIS Disconnector[J]. High voltageapparatus, 2019, 55(10): 247-252. DOI: 10.13296/j.1001-1609.hva.2019.10.040.
Analysis and Prevention Measures of Discharge Research of Insulated Pull Rod in GIS Disconnector
The flashover fault of VPI epoxy insulated pull rod in GIS disconnector is analyzed on the acceptance test.Electric field distribution is computed by Maxwell 3D simulation
results prove model design is a reasonable structure. Based on the detection methods of X-ray flaw detection and dissection and staining examination
the flashover reason has been found is that the insulated pull rod has internal air gaps. And then the influence of air gap defects at different parts of the insulated pull rod on the electric field distribution is analyzed by using Maxwell 3D simulation.According to the results
air gap defects close to the high voltage part are the most dangerous for electric field explosion. They are more likely to cause flashover. Based on the research achievements and according the feature of production process of insulated pull rod
the practical focus for the manufacturing process of insulated pull rod are proposed
to prevent that the insulated pull rod has internal bubbles or air gaps in the process of impregnate the adhesive composed of epoxy resin and liquid anhydride under vacuum pressure. At the same time
in the process of inspection of insulated pull rod
the strong light detection method is added to effectively screen the material defects
so the qualified rate of the parts can be guaranteed.