LUO Yuanxiang, HAN Tao, ZHANG Yonghui, et al. Relationship Between Excitation Current and Vibration of Transformer Under Different DC Disturbance[J]. High voltageapparatus, 2019, 55(11): 79-85.
LUO Yuanxiang, HAN Tao, ZHANG Yonghui, et al. Relationship Between Excitation Current and Vibration of Transformer Under Different DC Disturbance[J]. High voltageapparatus, 2019, 55(11): 79-85. DOI: 10.13296/j.1001-1609.hva.2019.11.011.
Relationship Between Excitation Current and Vibration of Transformer Under Different DC Disturbance
The relationship between excitation current and core vibration of the three-phase transformer with Y/Δ connection under DC disturbance was investigated in this study. Based on the three-phase transformer DC disturbance circuit
two state variables of dynamic inductance and time-domain current were calculated
the excitation current was identified by using transformer port measurement information
and the saturation state of transformer excitation was represented by excitation current. Electromagnetic coupling method was used to simulate the electromagnetic characteristics of the transformer under different DC disturbances. The excitation current and core vibration acceleration under AC/DC hybrid mode were calculated
the relationship between excitation current and core vibration characteristics was analyzed. Moreover
a DC disturbance experiment platform of 220 V three-phase transformer was established to collect excitation current and core vibration data of the transformer under different DC disturbances. The correctness of the simulation model was verified through comparison between the simulation results and the experimental data.