WU Xiaowen, LU Ling, HU Sheng, et al. Statistics and Analysis of Audible Noise Features of 110 kV Transformers[J]. High voltageapparatus, 2019, 55(11): 113-117+125.
WU Xiaowen, LU Ling, HU Sheng, et al. Statistics and Analysis of Audible Noise Features of 110 kV Transformers[J]. High voltageapparatus, 2019, 55(11): 113-117+125. DOI: 10.13296/j.1001-1609.hva.2019.11.016.
Statistics and Analysis of Audible Noise Features of 110 kV Transformers
Transformer noise is one of the critical parameter to diagnose its operation. In order to realize transformer operation condition evaluation based on noise test
field noise test is carried out on 72 110 kV transformers.Three features including the odd-even harmonic ratio
high-frequency energy ratio and spectral complexity are proposed. Statistical analysis is made to determine the data range in which these features are distributed in normal operation condition of the transformer with different cooling methods. In addition
the influence of operation time on the distribution of transformer noise features is analyzed. The result shows that cooling method has large influence on the average sound pressure level
odd-even harmonic ratio
high-frequency energy ratio and spectral complexity of transformer noise. These features of transformer with cooling fans are much higher than that of the transformer cooled with nature convection. Little influence is observed by the transformer operation time on these features. The results will be used as basic data and reference for the condition evaluation of transformers.