FANG Chun’en, LI Yuhao, CHEN Chuanjiang, et al. Optimal Instant for Controlled Switching of the Serially Compensated Transmission Lines Based on Prony Algorithm[J]. High voltageapparatus, 2019, 55(12): 15-22.
FANG Chun’en, LI Yuhao, CHEN Chuanjiang, et al. Optimal Instant for Controlled Switching of the Serially Compensated Transmission Lines Based on Prony Algorithm[J]. High voltageapparatus, 2019, 55(12): 15-22. DOI: 10.13296/j.1001-1609.hva.2019.12.003.
Optimal Instant for Controlled Switching of the Serially Compensated Transmission Lines Based on Prony Algorithm
which is added in the power system with large capacity and long distance
will weaken the line’s uniformity
lead to switching over-voltage on the line
and harm the insulation of electrical equipment.This study uses the controlled switching techniques to suppress the over-voltage of series compensation line according to the basic principle of generating over-voltage on no-load lines.The Prony algorithm is employed to predict the voltage crossing zero and determine the optimal closing instant.Reclosing models of the serially compensated transmission lines are built with the softwares PSCAD and MATLAB to simulate the transient process.The results verify the accuracy and feasibility of the Prony algorithm
and show that the controlled switching can effectively reduce the over-voltage of the serially compensated transmission line.In addition
the influences of the circuit breaker’s RDDS and the dispersity of closing times on the optimal closing instant is analyzed to obtain the optimal closing instants under different closing characteristics.