Analysis and Experiment Study on Dynamic Stability of Setup for Impulse Generator Protection Circuit Breaker Based on Tight Coupling Split Reactor[J]. High voltageapparatus, 2019, 55(12): 23-31.
Analysis and Experiment Study on Dynamic Stability of Setup for Impulse Generator Protection Circuit Breaker Based on Tight Coupling Split Reactor[J]. High voltageapparatus, 2019, 55(12): 23-31. DOI: 10.13296/j.1001-1609.hva.2019.12.004.
Analysis and Experiment Study on Dynamic Stability of Setup for Impulse Generator Protection Circuit Breaker Based on Tight Coupling Split Reactor
In order to analyze the dynamic stability performance of shunt vacuum circuit breaker based on high coupling split reactor
this paper introduces the principle and layout of shunt vacuum circuit breaker based on tight coupling reactor as high power laboratory impulse generator circuit breaker(GCB).Based on the layout
this paper calculates the short circuit dynamic stability of rectangular bus and insulator in theory
the electromagnet force exerts on the reactor terminal copper bar and bracket is analyzed in simulation
which prove the feasibility of this layout in theory.Finally type test on this setup is conducted
which prove the feasibility of this layout in experiment.Results in theory and experiment presents that the layout of this setup can meet the need of short circuit dynamic stability for large capacity laboratory test.