KANG Jun, QU Quanlei, LI Jun, et al. Development of 1500 kV AC Series Resonance Test System for High Altitude Test[J]. High voltageapparatus, 2019, 55(12): 120-124.
KANG Jun, QU Quanlei, LI Jun, et al. Development of 1500 kV AC Series Resonance Test System for High Altitude Test[J]. High voltageapparatus, 2019, 55(12): 120-124. DOI: 10.13296/j.1001-1609.hva.2019.12.017.
Development of 1500 kV AC Series Resonance Test System for High Altitude Test
对其中的关键部件串联电抗器进行了电场仿真计算。结果表明文中所研制的试验系统在1 500 kV运行时电晕放电量小于10 pC
可满足高海拔地区对特高压设备进行交流耐压及局部放电测量时使用。
Abstract
With the construction of UHV transmission project the construction of UHV AC and DC projects in Qinghai Tibet and other regions can transform the advantages of renewable resources such as wind and solar energy into electric energy and transport them to the load centers in the east and middle which can effectively alleviate electric energy distribution problem in China.In order to meet the needs of field test of UHV transmission project in high altitude areas such as Qinghai and Tibet this paper developed the first 1 500 kV AC series resonance test system for high altitude test in China.According to the special environmental conditions at the site the overall system composition was discussed.The electric field simulation calculation was performed on the key component series reactor.The results show that the test system developed in this paper has a corona discharge of less than 10 pC at 1 500 kV which can be used to measure AC withstand voltage and partial discharge of UHV equipment in high altitude areas.
Study on the Technical Problems of DC Filter for Qinghai-tibet DC Project
Research on Application of Microphone-optimized Spiral Arrays-based Acoustic Imaging Devices in Partial Discharge Localization
Study on Fiber Interferometric Partial Discharge Ultrasonic Sensing Method Based on Acoustic-optic Modulation and RF Phase Detection
High-frequency Sensing Technology of Partial Discharge of Switchgear Cabinet for Wind Solar & Energy Storage Stations in Gobi Deserts
Research on Influence of Piezoelectric Material Properties and Element Size on Sensitivity of Piezoelectric Sensor for Partial Discharge Monitoring of Transformer
Related Author
ZUO Qiang-lin
DENG Guang-zhao
FENG Chun-lin
FANG Ya-mei
YUE Song
GAO Fei
HAN Shuai
DONG Haoyuan
Related Institution
Guilin Power Capacitors Co.,Ltd.
Electric Power Research Institute of State Grid Tibet Company
China Electric Power Research Institute Co., Ltd.
Iflytek Co., Ltd.
Electric Power Research Institute, State Grid Hebei Electric Power Co., Ltd.