TIAN Yan, WANG Yong, YANG Sen, et al. UHF Partial Discharge Location Method Based on Time Delay Estimation of Linear Prediction Analysis[J]. High voltageapparatus, 2019, 55(12): 181-186.
TIAN Yan, WANG Yong, YANG Sen, et al. UHF Partial Discharge Location Method Based on Time Delay Estimation of Linear Prediction Analysis[J]. High voltageapparatus, 2019, 55(12): 181-186. DOI: 10.13296/j.1001-1609.hva.2019.12.026.
UHF Partial Discharge Location Method Based on Time Delay Estimation of Linear Prediction Analysis
The localization of partial discharge(PD) based on ultra-high frequency(UHF)signals has not been widely used in substations due to the excessive localization error
which is mainly introduced by the error of time delay measurement.A novel time delay estimation method based on linear prediction analysis is proposed in this paper.Linear prediction analysis is carried out on the actual PD signals.The power law is applied to the prediction error to highlight the time of PD occurrence.Eventually
the generalized correlation algorithm is used to estimate the signal time delay.The proposed method could estimate the signal time delay with high precision
thus improving the accuracy of PD localization.Experiment results show that the localization distance error is less than 1 meter and the localization angel error is less than 8 degrees