XIANG Changyuan, XIANG Zutao, XU Wenjia. TRV Characteristics of Post-breaker Circuit Breaker Based on High Coupling Split Reactor Current Limiter[J]. High voltageapparatus, 2020, 56(1): 18-23.
XIANG Changyuan, XIANG Zutao, XU Wenjia. TRV Characteristics of Post-breaker Circuit Breaker Based on High Coupling Split Reactor Current Limiter[J]. High voltageapparatus, 2020, 56(1): 18-23. DOI: 10.13296/j.1001-1609.hva.2020.01.003.
TRV Characteristics of Post-breaker Circuit Breaker Based on High Coupling Split Reactor Current Limiter
In order to solve the problem of excessive short-circuit current in the development of 500 k V power grid
acurrent limiting device based on high coupled split reactor is proposed
which can effectively limit short-circuit cur-rent and improve the breaking capacity of circuit breakers. However
there may be a problem that the transient recov-ery voltage of parallel circuit breakers exceeds the standard when non-synchronous breaking occurs. Firstly
thestructure and interruption process of current limiting device are analyzed. According to its components and operationcharacteristics
the transient recovery voltage of circuit breakers operating under different conditions is calculated byEMTP simulation platform
and the influence of current limiting device parameters on the transient recovery voltageis obtained. Then
a simulation model with 500 k V current limiter is built in an engineering example to verify the fea-sibility of the current limiter under different fault types. The simulation results show that the larger the reactor valuein the current limiting device
the higher the transient recovery voltage and the higher the rise rate of the circuitbreaker after non-synchronous interruption. Selecting the appropriate reactor value and shunting capacitor can effec-tively reduce the amplitude and rate of rise of the transient recovery voltage.