WANG Yu, YANG Zhongzhou, DAI Dongyun, et al. Insulation Structure Design of the Integration of Electronic Current Transformer and Circuit Breaker Contact Arm[J]. High voltageapparatus, 2020, 56(1): 48-54.
WANG Yu, YANG Zhongzhou, DAI Dongyun, et al. Insulation Structure Design of the Integration of Electronic Current Transformer and Circuit Breaker Contact Arm[J]. High voltageapparatus, 2020, 56(1): 48-54. DOI: 10.13296/j.1001-1609.hva.2020.01.008.
Insulation Structure Design of the Integration of Electronic Current Transformer and Circuit Breaker Contact Arm
This paper introduced the insulation structure design of integrated Electronic Current Transformer(ECT)with ZN□-12/D1250-31.5 high voltage AC Vacuum Circuit Breaker(VCB)
and focused on the insulation optimi-zation process. Based on the original size of switchgear、VCB and the new size of ECT
the electric field simulationmodel was built. In order to meet the insulation design requirements
the influencing factors of electric field distribu-tion were adjusted
such as relative location of electronic current transformer
VCB arm
epoxy resin thickness
shield arrangement
and epoxy resin encapsulated arm length. The integrated ECT and VCB prototype were tested inNational Quality Supervision and Inspection Center(XIHARI Test Station)
the experimental results verified the fea-sibility of the design scheme.