ZHOU Feng, ZHANG Dandan, LIU Hongjing, et al. Influence of Temperature on the Electric Field Distribution of the Winding End in Converter Transformer[J]. High voltageapparatus, 2020, 56(1): 80-86.
ZHOU Feng, ZHANG Dandan, LIU Hongjing, et al. Influence of Temperature on the Electric Field Distribution of the Winding End in Converter Transformer[J]. High voltageapparatus, 2020, 56(1): 80-86. DOI: 10.13296/j.1001-1609.hva.2020.01.013.
Influence of Temperature on the Electric Field Distribution of the Winding End in Converter Transformer
In order to grasp the electric field distribution of the oil-paper insulation structure in converter transform-er at different temperature
the dielectric properties of transformer oil and pressboard are measured at the tempera-ture range of-40~+50 ℃. In addition
for the 500 kV converter transformer
the temperature characteristics of elec-tric field at the end of the winding under AC test voltage and DC test voltage are studied by finite element analysis.The results show that temperature affects the electric field distribution at the end of the winding by affecting the di-electric properties of the oil-paper insulation. In consideration of the temperature variation in the actual operation
the factory test of the converter transformer needs to be corrected.