LIU Yugen, CHEN Chao, YANG Ruijing, et al. Location Method of Ground Fault in DC System of Substation Based on Wavelet Relative Entropy[J]. High voltageapparatus, 2020, 56(1): 169-174.
LIU Yugen, CHEN Chao, YANG Ruijing, et al. Location Method of Ground Fault in DC System of Substation Based on Wavelet Relative Entropy[J]. High voltageapparatus, 2020, 56(1): 169-174. DOI: 10.13296/j.1001-1609.hva.2020.01.025.
Location Method of Ground Fault in DC System of Substation Based on Wavelet Relative Entropy
The state of DC system of substation is directly related to the normal operation of substation. To locate theground fault occurred in the DC system of substation rapidly
a new method to locate ground fault based on waveletrelative entropy is proposed in this paper. This method firstly decomposes the leakage current of each branch of theDC system though wavelet packet transform
and introduces theory of wavelet relative entropy. Then
the relative en-tropy of each branch is calculated when the ground fault occurs in the DC system with the spectral characteristics ofthe leakage current collected from each branch at normal operation condition as the reference sequence. And theground fault is considered to occur in the branch which has maximal wavelet relative entropy. Build a simulation mod-el in the PLECS software and make simulation. The simulation results show that the new location method for groundfault which is suitable for both of DC systems with good insulation performance or bad insulation performance.