Diagnostic Method to Determine Degree and Type of Winding Deformation in Power Transformer Based on Euclidean Distance
Frequency response analysis method is commonly used to monitor and diagnose the integrity of winding in Power transformer. Nearly a decade of research has prompted testing process of frequency response method toward standardization
but a suitable algorithm for quantitative analysis of curve data still needs further study. In this paper
the quantitative analysis of frequency response curve data can be regarded as a probability classification problem
so the euclidean distance analysis is put forward to determine degree and type of winding deformation in power transformer. The results show that euclidean distance analysis could effectively diagnose the degree of winding deformation and has higher linearity of degree compared with other mathematical index in previous studies. Besides
euclidean distance of segmented frequency band is firstly calculated separately after discretization of the full spectrum and then the ratio of maximum and minimum could be calculated to determine the type of winding deformation. The research results has a certain reference value for quantitative analysis of frequency response curve data.